Add to Cart
Product Information
Controller Type | Single slot CPU module with embedded Ethernet Interface |
Processor | |
Processor Speed | 133 MHz |
Processor Type | AMD SC520 |
Execution Time (Boolean Operation) | 0.15 msec per Boolean instruction |
Type of Memory Storage | RAM and Flash |
Memory | |
User Memory (total) | 240KB (245,760) Bytes |
Note: Actual size of available user program memory depends on the amounts configured for %R, %AI, and %AQ word memory types. | |
Discrete Input Points - %I | 2,048 (fixed) |
Discrete Output Points - %Q | 2,048 (fixed) |
Discrete Global Memory - %G | 1,280 bits (fixed) |
Internal Coils - %M | 4,096 bits (fixed) |
Output (Temporary) Coils - %T | 256 bits (fixed) |
System Status References - %S | 128 bits (%S, %SA, %SB, %SC - 32 bits each) (fixed) |
Register Memory - %R | Configurable 128 to 32,640 words |
Analog Inputs - %AI | Configurable 128 to 32,640 words |
Analog Outputs - %AQ | Configurable 128 to 32,640 words |
System Registers - %SR | 28 words (fixed) |
Timers/Counters | >2,000 (depends on available user memory) |
Hardware Support | |
Battery Backed Clock | Yes |
Battery Back Up (Number of months with no power) | 1.2 months for internal battery (installed in the power supply) 15 months with external battery (IC693ACC302) |
Load Required from Power Supply | 7.4 watts of 5VDC. High Capacity power supply required. |
Hand Held Programmer | CPU374 does not support Hand Held Programmer |
Program Store Devices supported | PLC Program Download Device (PPDD) and EZ Program Store Device |
Total Baseplates per System | 8 (CPU baseplate + 7 expansion and/or remote) |
Software Support | |
Interrupt Support | Supports the periodic subroutine feature. |
Communications and Programmable Coprocessor Compatibility | Yes |
Override | Yes |
Floating Point Math | Yes, hardware floating point math |
Communications Support | |
Built-in Serial Ports | No serial ports on CPU374. Supports RS-485 port on power supply. |
Protocol Support | SNP and SNPX on power supply RS-485 port |
Built-in Ethernet Communications | Ethernet (built-in) – 10/100 base-T/TX Ethernet Switch |
Number of Ethernet Ports | Two, both are 10/100baseT/TX ports with auto sensing. RJ-45 connection |
Number of IP Addresses | One |
Protocols | SRTP and Ethernet Global Data (EGD) and channels (producer and consumer); Modbus/TCP Client/Server |
EGD Class II Functionality (EGD Commands) | Supports acknowledged singe command transfers (sometimes referred to as “datagrams”) and Reliable Data Service (RDS – a delivery mechanism to make sure a command message gets through once and only once). |
SRTP Channels | Up to 16 SRTP Channels Up to 36 SRTP/TCP connections total, consisting of up to 20 SRTP Server connections and up to 16 Client Channels. |